30 mrt

SSC Maintenance

Startdate: March 18th 2012 17:00:00 (CEST)
Enddate: March 19th 2012 02:00:00 (CEST)

Dear customer,

Please note that due to maintenance, it’s possible the secure.leaseweb.com will not be reachable within the given timeframe.

The maintenance will take place on Sunday March 18 between 17:00 and Monday March 19 02:00 (UTC/GMT +1 hour).

Kind regards,

Leaseweb NOC

30 mrt

SSC Maintenance window [Update]

Startdate: March 26th 2012 23:00:00 (CEST)
Enddate: March 27th 2012 00:00:00 (CEST)

Dear customer,

This Monday March 26th between 23:00 and 00:00 (UTC/GMT +1 hour) we will perform maintenance on two of our internal systems.
During this window you will not be able to use the following features in the Self Service Center:

– Rescue mode for dedicated servers
– Reinstallations for dedicated server
– Power on/off for dedicated servers

If you need to perform one of the above actions during this window please contact technical support at [email protected] and they will be able to provide you with further assistance.

If you experience any issues after this window please report a ticket by using the SSC. We will inform you through the SSC when you will be able to use above features again.

Kind regards,

LeaseWeb NOC

[UPDATE 27-03-2012 00:09 CET: The maintenance has been completed successfully]

30 mrt

[20120301] Emergency Power maintenance nameservers Frankfurt [Update]

Startdate: March 1st 2012 14:30:00 (CEST)
Enddate: March 1st 2012 15:00:00 (CEST)

Emergency Power maintenance affecting caching nameservers Frankfurt:

today (1 March 2012) the LeaseWeb team needs to perform emergency maintenance
on the racks that contain the caching nameservers in Frankfurt.

The expected downtime will be approx. 15 minutes per server.
The affected systems are:
– nscache07.leaseweb.net (178.162.151.40)
– nscache09.leaseweb.net (178.162.151.41)

One by one, they will be moved to a different location.
If your server uses only one of these 2 IP addresses,
please make sure to add the second IP address as well.
This will ensure resolving of domain names is still possible,
by using the alternative nameserver.

Kind regards,

LeaseWeb – NOC

UPDATE 15:01
Both systems have been moved to their new location and are up and running.

30 mrt

Uplink Maintenance High Volume Router Wuppertal

Startdate: March 5th 2012 08:00:00 (CEST)
Enddate: March 5th 2012 09:30:00 (CEST)

Dear customer,

During this maintenance window we will move on of the routers Uplink to a different LineCard.

You may notice short packet loss or downtime up to 5 minutes within the maintenance window.

Kind regards,

LeaseWeb – NOC

Sehr verehrte Kunden,

während der Wartungsarbeiten werden wir eine Uplink Verbindung auf eine andere Linecard umziehen.

Es kann sein das das für einen Zeitraum von 5 Minuten Packetverluste oder höhere Antwortzeit auftreten.

Mit freundlichen Grüssen

LeaseWeb – NOC

30 mrt

[20120306] LOFT US high volume router upgrade [Update]

Startdate: March 6th 2012 12:00:00 (CEST)
Enddate: March 6th 2012 13:00:00 (CEST)

Dear customer,

As part of our commitment to continually improve the level of service you receive from LeaseWeb we are undertaking this maintenance. During the maintenance we will upgrade the software on one of the high volume routers.

You will experience short downtime up to 15 minutes within the maintenance window.

The affected ranges are below:
Volume Network:
-108.59.3.0/24
-108.59.4.0/24
-108.59.7.0/24
-108.59.8.0/22
-108.59.13.0/24
-108.59.14.0/24
-199.58.84.0/22
-2604:9A00:2010::/44

The maintenance will take place on the 6th of March, 2012 between 12:00 CET, 6:00 AM EST (Manassas, Virginia) and 13:00 CET, 07:00 AM EST (Manassas, Virginia) time.

Kind regards,

LeaseWeb NOC

[UPDATE 12:20CET / 06:20 EST] The upgrade has been performed successfully.

30 mrt

Maintenance Leaseweb.com and SSC

Startdate: March 7th 2012 00:00:00 (CEST)
Enddate: March 7th 2012 06:00:00 (CEST)

Dear customer,

Please note that due to maintenance, it’s possible the www.leaseweb.com and secure.leaseweb.com will not be reachable within the given timeframe.
The maintenance will take place on Wednesday March 7 between 00:00 and 06:00 (UTC/GMT +1 hour).

Kind regards,

Leaseweb NOC

30 mrt

Evoswitch high volume router maintenance [Update]

Startdate: February 28th 2012 06:00:00 (CEST)
Enddate: February 28th 2012 07:00:00 (CEST)

Dear Customer,

As part of our commitment to continually improve the level of service you receive from LeaseWeb we are undertaking this maintenance.

During this maintenance window we will replace routing engines of one of our high volume routers.

You may notice short packet loss or downtime up to 15 minutes within the maintenance window.

Affected IP ranges:

62.212.72.0/23
62.212.82.0/24
62.212.85.0/24
62.212.88.0/23
82.192.94.0/23
83.149.70.0/23
83.149.124.0/22
85.17.24.0/21
95.211.136.0/21
95.211.144.0/20
2001:1af8:4010::/44

Kind regards,

LeaseWeb – NOC

[UPDATE 7:15]
Faulty linecard blocked router fabric and caused some destination to be unreachable. The linecard was swapped before the maintenance window had ended. Please open a support ticket should you see any further problems.

30 mrt

Major maintenance on cooling installation Schuberg Philis datacenter [Update]

Startdate: February 27th 2012 00:00:00 (CEST)
Enddate: March 20th 2012 00:00:00 (CEST)

Introduction:

The Schuberg Philis datacenter is being prepared for a major change in its cooling system. This change will ensure higher cooling efficiency within the datacenter, as well as more future capacity available within the datacenter.

At the time of the maintenance, parts of the cooling system will be reconnected to new cooling units. During the actual maintenance, limited cooling capacity will be available for the datacenter room which is being upgraded. Since the Schuberg Philis datacenter is fully redundant in terms of cooling systems and cooling capacity, the datacenter will make use of this redundancy to perform the maintenance.

Cooling redundancy and capacity tests for each dataroom have already been executed successfully. Schuberg Philis does not expect any cooling issues during the maintenance, but still they have taken additional measures in case of unexpected cooling issues during the maintenance. (E.g. failure of a datacenter room pump, etc).

The maintenance will take place in February and March of 2012.

Schedule:

27th of february ( four airco’s )
2nd of march ( four airco’s )
20th of march ( four airco’s )
14th march ( four airco’s )

——UPDATE——

All maintenance windows are completed successfully without unexpected cooling issues.

30 mrt

Network Issues in FRA – Databurg [Update]

Time: March 28th 2012 16:12:00 (CEST)
Update: 17:50

Cause was identified and we are taking steps in addressing the issue.

Update: 17:15

Problem was isolated and we are taking steps in restoring full network stability.
A small number of servers from the initially affected section are currently unreachable.
Next Update at 17:45

Update: 17:00

Investigation is still ongoing, next update in 30min.
Sorry for the inconvenience caused.

Update since 22:00

The issue have been resolved and everything should be up-and-running. Also steps have been taking for possible events in the future too address this sooner. If you still have issues, please contact us at [email protected]

Expected Downtime: Unknown
Location: Frankfurt Databurg
Affected IP ranges: see below
Under investigation / Unknown
*******************************
Dear customer,

At the moment we experience some troubles on a small part of our network in Frankfurt.
A small portion of our customers can experience service degradation or service interruption.
We are doing our utmost to solve this issue a.s.a.p.
As soon as we have more information available, we will publish it here.

Affected ranges
1 212.95.32.0/19
2 84.16.224.0/19
4 95.168.160.0/19
5 78.159.96.0/19
7 188.72.192.0/18
8 91.191.160.0/21
10 178.162.128.0/17
11 77.223.144.0/23
12 46.166.152.0/21
14 217.73.56.0/21
15 176.65.160.0/21
16 46.166.151.0/24
17 37.58.48.0/20
18 37.1.216.0/21

Please be patient while we are working on this problem.

Regards,
LeaseWeb BV

30 mrt

Network Outage in FRA – Databurg [Update]

Time: March 27th 2012 20:58:00 (CEST)
Final Update: 28-03-2012 12:00
The root cause of the network issue was due to very large lldp multicast loop-flood.
This type of network issue was very difficult to detect and took a long time to pin-point. We will in the near future plan a maintenance in to replace some hardware that will restrict this type of outage.

Our apologies for any inconvenience caused.

Update: 23:10

Currently 95% of the connected customers are back online, we are still investigating a small network segment.
We will continue to make updates as new information is available.

Update: 22:20

We have reduced the network issue down and 80% of all affected server are back online.
We are now trouble shooting the issue on the last affect segment.
We will continue to make updates as new information is available.

Update: 22:00

Investigation is still ongoing, the cause the network outage is still not known.
We will continue to make updates as new information is available.

Update: 21:25

Network engineer is onsite, still investigating the issue.
We will continue to make updates as new information is available.

Sorry for the inconvenience caused.

Expected Downtime: Unknown
Location: Frankfurt Databurg
Affected IP ranges: see below
Under investigation / Unknown
*******************************
Dear customer,

At the moment we experience some troubles on part of our network in Frankfurt

We are doing our utmost to solve this issue a.s.a.p.
As soon as we have more information available, we will publish it here.

Affected ranges
1 212.95.32.0/19
2 84.16.224.0/19
4 95.168.160.0/19
5 78.159.96.0/19
7 188.72.192.0/18
8 91.191.160.0/21
10 178.162.128.0/17
11 77.223.144.0/23
12 46.166.152.0/21
14 217.73.56.0/21
15 176.65.160.0/21
16 46.166.151.0/24
17 37.58.48.0/20
18 37.1.216.0/21

Please be patient while we are working on this problem.

Regards,
LeaseWeb BV

*********************************************************************************
German Translation:

Sehr geehrte Kunden,

momentan haben wir Probleme in Teilen unseres Netzwerkes in Frankfurt.

Wir werden das Beste machen, um das Problem schnellst möglichst zu beheben.
Sobald wir neue Informationen haben, werden wir sie hier für Sie bereitstellen.

Folgende IP – Adressbereiche sind von dem Ausfall betroffen:

1 212.95.32.0/19
2 84.16.224.0/19
4 95.168.160.0/19
5 78.159.96.0/19
7 188.72.192.0/18
8 91.191.160.0/21
10 178.162.128.0/17
11 77.223.144.0/23
12 46.166.152.0/21
14 217.73.56.0/21
15 176.65.160.0/21
16 46.166.151.0/24
17 37.58.48.0/20
18 37.1.216.0/21

Bitte gedulden Sie sie noch etwas während wir an dem Problem arbeiten.

Mit freundlichen Grüßen

Leaseweb Germany GmbH